MODBUS_TCP_PI_LISTEN(3) | libmodbus Manual | MODBUS_TCP_PI_LISTEN(3) |
NAME¶
modbus_tcp_pi_listen - create and listen a TCP PI Modbus socket (IPv6)SYNOPSIS¶
int modbus_tcp_pi_listen(modbus_t *ctx, int nb_connection);DESCRIPTION¶
The modbus_tcp_pi_listen() function shall create a socket and listen to maximum nb_connection incoming connections on the specified nodes. The context ctx must be allocated and initialized with modbus_new_tcp_pi(3) before to set the node to listen, if node is set to NULL or 0.0.0.0, any addresses will be listen.RETURN VALUE¶
The function shall return a new socket if successful. Otherwise it shall return -1 and set errno.EXAMPLE¶
For detailed examples, see source files in tests directory:•unit-test-server.c, simple but handle only one
connection
... ctx = modbus_new_tcp_pi("::0", "502"); s = modbus_tcp_pi_listen(ctx, 1); modbus_tcp_pi_accept(ctx, &s); for (;;) { rc = modbus_receive(ctx, query); modbus_replay(ctx, query, rc, mb_mapping); } ... mclose(s); modbus_free(ctx);
•bandwidth-server-many-up.c, handles several
connections at once
SEE ALSO¶
modbus_new_tcp_pi(3) modbus_tcp_pi_accept(3) modbus_tcp_listen(3)AUTHORS¶