APCSMART(8) | NUT Manual | APCSMART(8) |
NAME¶
apcsmart - Driver for American Power Conversion Smart Protocol UPS equipmentSYNOPSIS¶
apcsmart -h apcsmart -a 'UPS_NAME' [-x option=value ...]SUPPORTED HARDWARE¶
The apcsmart driver should recognize (or at the very least work with) majority of Smart-UPS models - which includes Smart-UPS, Matrix-UPS and Back-UPS lineups, among few other ones. Currently we can roughly divide APC hardware into 3 groups (note that the division isn't strict by any means, and the borders between those are pretty fuzzy): [very] "old" modelsThese models usually have old APC logo, white color and
no programmable eeprom; You won't find them listed anywhere on
APC’s site either. The support for those will be usually based on
driver's compatibility tables, or if the model (firmware) is not listed in
those - the driver will try to follow the very basic subset of features, while
still trying to remain useful. Despite "smart" tagname, they often
tend to behave in pretty dumb way (see the section below about shutdown
behaviour).
Example models:
"new" models
•Smart-UPS 2000I
•Smart-UPS 900I
These models usually come from late 1990s / pre-2009
times. They are often referred as "3rd. gen". For the most part,
they have programmable eeprom, report supported commands and capabilites, and
should work just fine with the apcsmart driver.
"microlink" models
WARNING: these are not natively supported by
apcsmart (or apcupsd for that matter, if you’re wondering). Around 2007
APC (now APC Schneider) decided to go back to its proprietry roots and all the
new models (SMT, SMX, SURTD) use completely different protocol and cables. If
you purchased a new APC UPS, that uses cable with rj45 on the one end, and
db-9 on the other - then you have such model. Your only option to support it
through NUT is to purchase "legacy communications card" -
part #AP9620 (google 'AP9620' for more details). Or if that's not an option,
rely on official software.
Another thing to remember is that Smart protocol is not USB protocol. If you
have UPS with both USB and serial ports, then depending on how you connect it,
you will need either apcsmart or usbhid-ups driver.
CABLING¶
This driver expects to see a 940-0024C cable or a clone by default. You can switch to the 940-0095B dual-mode cable support with the 'cable=' definition described below. If your 940-xx24X cable is broken or missing, use this diagram to build a clone: http://www.networkupstools.org/cables.html#_940_0024c_cloneTTY MODES¶
By default the driver works in canonical mode, but it showed to be a problem in windows systems. Furthermore there’s a possibility of some obscure serial cards or serial-usb convertes that could cause problems as well. You can use 'ttymode=' option to force non-canonical discipline in ups.conf(5): ttymode=raw Alternatively, you can also provide it on the command line using: -x ttymode=rawEXPLANATION OF SHUTDOWN METHODS SUPPORTED BY APC UPSES¶
APC hardware supports a lot of shutdown methods, that themselves can differ in behaviour quite a bit, depending on the model. S (soft hibernate)This is most basic command present in probably all APC
models. It will hibernate the UPS, and subsequently wake it up when the mains
supply returns. The command doesn't work if UPS is running on mains.
"old" models
CS (aka "force OB hack")
The behaviour here is unfortunately pretty primitive -
when the power returns, the UPS just wakes up. No grace periods, no min.
battery charge condition, etc. This is probably not what you want.
"new" models
The behaviour here is as expected - the power is cut off
after the eeprom defined grace period. The UPS will wake up when the power
returns, after the eeprom defined delay AND if the eeprom defined min. battery
charge level is met. The delay is counted from the power's return.
This is a trick to make UPS power down even if it's
running on mains. Immediately before issuing S, "simulate power
failure" is issued. The remaining behaviour is as in S case.
The name came from APC CS models, where such trick was used to power down UPSes
in consistent fashion using only S. It's better to use @nnn
command if your UPS supports it (and is not too old, see below).
@nnn (hard hibernate)
This is basic command used to hibernate UPS regardless if
it's running on batteries or on mains. The option takes 3 digits argument
which can be used to specify additional wakeup delay (in 6 minute units).
"old" models
K (delayed poweroff)
The behaviour is - unfortunately - similary primitive to
S. The UPS unconditionally wakes up after nnn*6 minutes - it doesn't
care if the power returned ! If nnn = 000, then UPS will do precisely
nothing. On those models you're better specifying nnn > 0, if you can
estimate the kind of power problems that might be happening in your
environment. Another thing to consider with "old" models - you might
lose the connection with the UPS, until it wakes up (with S, the serial
connection is kept alive).
"new" models
All the usual variables defined in eeprom are respected
(see S). Additionally, if nnn > 0, the nnn*6 minutes are added to
eeprom defined delay. UPS will not power up if it's running on batteries,
contrary to what "old" models used to do - the combined delay is
counted from the moment of power return.
Supposedly there exist models that take 2 digits instead of 3. Just in case, NUT
also supports such variation. You have to provide exactly 2 digits to trigger
it ( awd option, or argument to one of the supported instant
commands).This is permanent poweroff - the UPS will not wake up
automatically. On newer units, it will respect applicable eeprom
variables.
Z (instant poweroff)
This is also permanent poweroff - the UPS will not wake
up automatically. The poweroff is executed immediately.
SHUTDOWN CONTROL BY NUT¶
There are three options used to control the shutdown behaviour. sdtype=[0-5]This option takes a single digit (0-5) as an argument.
See below for details.
advorder=no|[0-4]+
This option takes string of digits as an argument.
Methods listed are tried in turn until one of them succeedes. Note that the
meaning of digits is different from sdtype. See below for
details.
awd=[0-9]{1,3}
This option lets you specify additional wakeup delay used
by @. If you provide exactly 2 digits, the driver will try 2 digits
variation (see previous section for more info). Otherwise standard 3 digits
variation is used. Note: the time unit is 6 minutes !
Keep in mind that sdtype and advorder are mutually exclusive. If
advorder is provided, sdtype is ignored. If advorder is
set to 'no', sdtype is used instead.
If nothing is provided, NUT will assume sdtype=0 - which is
generally fine for anything not too ancient or not too quirky.
SDTYPE¶
The values permitted are from 0 to 5. Only one can be specified. Anything else will cause apcsmart to exit. 0issue soft hibernate (S) if the UPS is running on
batteries, otherwise issue hard hibernate ( @)
1
issue soft hibernate (S) (if on batteries), and if
it fails (or on mains) - try hard hibernate ( @)
2
issue instant poweroff (Z)
3
issue delayed poweroff (K)
4
issue "force OB hack" (CS)
5
issue hard hibernate (@)
ADVORDER¶
The argument is either a word 'no', or a string of 1 - 5 digits in [0 - 4] range. Each digit maps to the one of shutdown methods supported by APC UPSes. Methods listed in this way are tried in order, until one of them succedes. If advorder is undefined or set to 'no', sdtype is used instead. The mapping is as follows:0 | soft hibernate (S) |
1 | hard hibernate (@) |
2 | delayed poweroff (K) |
3 | instant poweroff (Z) |
4 | "force OB hack" (CS) |
IGNORING LB STATE¶
APC units - even if they report LB mode - will not go into shutdown automatically. This gives us even more control with reference to "when to actually shutdown psu". Since version 2.6.2, NUT supports ignorelb option in driver's section of ups.conf(5). When such option is in effect, the core driver will ignore LB state as reported by specific driver and start shutdown basing the decision only on two conditions: battery.charge < battery.charge.low OR battery.runtime < battery.runtime.low Of course - if any of the variables are not available, the appropriate condition is not checked. If you want to explicitly disable one of the conditions, simply override the right hand variable causing the condition to always evaluate to false (you can even provide negative numbers). APC UPSes don't have battery.charge.low - you will have to define it if you want to use such condition (prefix the variable with override. or default.). "New" units have battery.runtime.low, but depending on battery quality, firmware version, calibration and UPS load - this variable can be underestimated quite a bit - especially right after going into OB state. This in turn can cause LB to be asserted, which under normal conditions will cause NUT to initiate the shutdown. You might want to disable this condition entirely, when relying on ignorelb option (this was actually the main motivation behind introduction of such feature). Simple example:[apc] ignorelb override.battery.charge.low = 15 override.battery.runtime.low = -1
SUPPORTED INSTANT COMMANDS¶
The apcsmart driver exposes following instant commands: shutdown.returnexecutes soft hibernate
shutdown.return cs
executes "force OB hack"
shutdown.return at:<nbr>
executes "hard hibernate" with <nbr>*6
minutes additional wakeup delay (<nbr> format is the same as of
awd option)
shutdown.stayoff
executes "delayed poweroff"
load.off
executes "instant poweroff"
All the above commands must be issued 2nd time to have any effect (no less than
3 seconds, and no more than 15 seconds after the initial call). Those commands
are mostly useful for manual testing, when your machine is not powered by the
UPS you're testing.
Other supported commands:
•load.on
•test.panel.start
•test.failure.start
•test.battery.start
•test.battery.stop
•bypass.start
•bypass.stop
•calibrate.start
•calibrate.stop
PREVIOUS DRIVER VERSION¶
Previous driver is still available as apcsmart-old - should there be any need to use earlier version (bugs, incompatiblities with new functionality, etc.). In due time apcsmart-old will be phased out completely, but this won’t happen until the new version gets solid exposure with no pending issues.BUGS¶
Some older APC UPS models return bogus data in the status register during a front panel test. This is usually detected and discarded, but some other unexpected values have occasionally slipped through. APC UPS models with both USB and serial ports require a power cycle when switching from USB communication to serial, and perhaps vice versa.AUTHOR¶
Nigel Metheringham <Nigel.Metheringham@Intechnology.co.uk> (drawing heavily on the original apcsmart driver by Russell Kroll). This driver was called newapc for a time and was renamed in the 1.5 series. In 2.6.2 it was renamed to apcsmart-old, being superseded by updated version with new features, which is maintained by Michal Soltys <soltys@ziu.info>SEE ALSO¶
nutupsdrv(8), ups.conf(5)Internet resources:¶
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/02/25/2014 | Network UPS Tools 2.7.1. |