table of contents
| MODBUS_NEW_TCP(3) | Libmodbus Manual | MODBUS_NEW_TCP(3) |
NAME¶
modbus_new_tcp - create a libmodbus context for TCP/IPv4SYNOPSIS¶
modbus_t *modbus_new_tcp(const char *ip, int port);DESCRIPTION¶
The modbus_new_tcp() function shall allocate and initialize a modbus_t structure to communicate with a Modbus TCP/IPv4 server.The ip argument specifies the IP address of the server to which the client wants etablish a connection.
The port argument is the TCP port to use. Set the port to MODBUS_TCP_DEFAULT_PORT to use the default one (502). It’s convenient to use a port number greater than or equal to 1024 because it’s not necessary to have administrator privileges.
RETURN VALUE¶
The modbus_new_tcp() function shall return a pointer to a modbus_t structure if successful. Otherwise it shall return NULL and set errno to one of the values defined below.ERRORS¶
EINVALAn invalid IP address was given.
EXAMPLE¶
modbus_t *ctx;
ctx = modbus_new_tcp("127.0.0.1", 1502);
if (ctx == NULL) {
fprintf(stderr, "Unable to allocate libmodbus context\n");
return -1;
}
if (modbus_connect(ctx) == -1) {
fprintf(stderr, "Connection failed: %s\n", modbus_strerror(errno));
modbus_free(ctx);
return -1;
}
SEE ALSO¶
modbus_new_rtu(3) modbus_free(3)AUTHORS¶
The libmodbus documentation was written by Stéphane Raimbault <stephane.raimbault@gmail.com[1]>NOTES¶
- 1.
- stephane.raimbault@gmail.com
mailto:stephane.raimbault@gmail.com
| 11/30/2016 | libmodbus 3.0.6 |