BESTUPS(8) | NUT Manual | BESTUPS(8) |
NAME¶
bestups - Driver for Best Power / SOLA (Phoenixtec protocol) UPS equipmentNOTE¶
This man page only documents the hardware-specific features of the bestups driver. For information about the core driver, see nutupsdrv(8).SUPPORTED HARDWARE¶
bestups was designed to monitor Best Power UPS hardware like the Fortress, Fortress Telecom, Axxium Rackmount and Patriot Pro. It also recognizes and supports SOLA units such as the 325, 520 and 620. In addition, the Best 610 is supported using the ‘ID’ option.EXTRA ARGUMENTS¶
This driver supports the following optional settings in the ups.conf(5): nombattvolt=numOverride the battery float voltage which is
normally determined by asking the hardware. This is useful if your UPS
constantly reports battery.charge values just below 100% even when it’s
completely charged.
If you have this problem, set this to whatever battery.voltage reports when the
UPS is known to be completely charged with a good battery.
The author’s Best Fortress 750 uses nombattvolt=27.4.
battvoltmult=num
Multiply the reported battery voltage by this
number. Some devices report only a fraction of the total battery voltage.
For example, the SOLA 610 700VA UPS (with a 24V battery) reports the single cell
voltage (about 2.27V when fully charged). In this particular case you can set
battvoltmult = 12 in ups.conf(8) to fix this.
ID=string
Set the Identification response string. This
should only be used with hardware that supports the Phoenixtec protocol status
inquiry commands, but not the "ID" command, such as the Best/SOLA
610. Format of the ID string is: AAA,BBBB,CCC,DDD,EE.E,FF.F
AAA is the three-character identification for the UPS model.
BBBB is the output power in VA (volt amperes). B is an integer number ranging
from 0 to 9.
CCC is the Nominal Input Voltage. C is an integer number ranging from 0 to 9.
The unit is Volts AC.
DDD is the Nominal Output Voltage. D is an integer number ranging from 0 to 9.
The unit is Volts AC.
EE.E is the Battery Voltage that will cause the UPS to shut itself off. E is an
integer number ranging from 0 to 9. Then unit is Volts DC and a decimal point
is present.
FF.F or FFF.F is the Battery Voltage at full charge. F is an integer number
ranging from 0 to 9. Then unit is Volts DC. Typically, for 700VA, 1KVA and
1.5KVA units, the format is FF.F. For 2KVA and 3KVA units, the format is
FFF.F.
Example: a Best 610 1.5KVA unit would use the string
"610,1500,120,120,10.0,48.0".
BUGS¶
The battery charge percentage value (in battery.charge) is derived from the voltage data that the UPS returns, since the UPS doesn’t return that value directly. On some hardware, the charge will remain at 100% for a long time and then drops quickly shortly before the battery runs out. You can confirm from the battery.voltage readings that this is a problem with the UPS and not this driver.AUTHOR¶
Russell Kroll, Jason WhiteSEE ALSO¶
The core driver:¶
nutupsdrv(8)Internet resources:¶
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/05/21/2012 | Network UPS Tools |