CLONE(8) | NUT Manual | CLONE(8) |
NAME¶
clone - UPS driver cloneNOTE¶
This man page only documents the specific features of the clone driver. For information about the core driver, see nutupsdrv(8).DESCRIPTION¶
This driver, which sits on top of another driver socket, allows users to group clients to a particular outlet of a device and deal with this output as if it was a normal UPS.EXTRA ARGUMENTS¶
This driver supports the following settings: load.off=commandRecommended. Set the command on the
"real" UPS driver that will be used to switch off the outlet. You
need both load.off and load.on in order to power cycle the
outlet. Otherwise, shutting down the clients powered by an outlet is a one way
street (see IMPORTANT).
load.on=command
Recommended. Set the command on the
"real" UPS driver that will be used to switch on the outlet. You
need both load.off and load.on in order to power cycle the
outlet. Otherwise, shutting down the clients powered by an outlet is a one way
street (see IMPORTANT).
load.status=value
Recommended. Set the variable on the
"real" UPS driver that will be used to indicate the outlet status
(i.e. on/off). If not specified, the clone driver will attempt to keep track
of the outlet status, but this is less reliable.
offdelay=num
Set the timer (in seconds) before the outlet
is turned off after the shutdown condition (OB LB) for this outlet is met or a
command to shutdown was issued. Defaults to 120 seconds.
ondelay=num
Set the timer (in seconds) for the outlet to
switch on in case the power returns after the oulet has been switched off.
Defaults to 30 seconds.
mincharge=value
Set the remaining battery level when the clone
UPS switches to LB (percent).
minruntime=value
Set the remaining battery runtime when the
clone UPS switches to LB (seconds).
IMPLEMENTATION¶
The port specification in the ups.conf(5) reference the driver socket that the "real" UPS driver is using. For example:[realups] driver = usbhid-ups port = auto
[clone-outlet-1] driver = clone port = usbhid-ups-realups load.on = outlet.1.load.on load.off = outlet.1.load.off load.status = outlet.1.status [...]
IMPORTANT¶
Unlike a real UPS, you should not configure a upsmon master for this driver. When a upsmon master sees the OB LB flags and tells the upsd server it is OK to initiate the shutdown sequence, the server will latch the FSD status and it will not be possible to restart the systems connected without restarting the upsd server.CAVEATS¶
The clone UPS will follow the status on the real UPS driver. You can only make the clone UPS shutdown earlier than the real UPS driver, not later. If the real UPS driver initiates a shutdown, the clone UPS driver will immediately follow.AUTHOR¶
Arjen de Korte <adkorte-guest@alioth.debian.org>SEE ALSO¶
upscmd(1), upsrw(1), ups.conf(5), nutupsdrv(8)Internet Resources:¶
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/05/21/2012 | Network UPS Tools |